Welcome To E POWER TECHNOLOGIES

EP IG+ SERIES

3Phase Input / 1Phase output

10 KVA - 60KVA

Application

IT INFRATRUCTURE

TELECOM

MEDICAL EQUIPMENT

DATA PROCESSING EQUIPMENT

MACHINE TOOLS & ROBOTICS

BANK & FINANANCE

FEATURES

Microprocessor based intelligent UPS system suitable for IT and Medical Equipment Load with unity power factor and a wide input voltage Window of 140-300 with an overall efficiency reaching 95%.

True online Double Conversion Topology.
The peak surge handling capacity of 300% for 3000msc.
True Inbuilt Isolation Transformer by design@ output.
IGBT based Rectifier & charger.
Control Designed to withstand all kinds of load.
Intelligent Battery Management to Prolong Battery Life Cycle.

High Input Power factor >0.99.
High Reliability Digital control.
N+1 hot standby option up to 10units
Wide Input Voltage Range.
Inbuilt Manual Bypass Switch.
Emergency Power off (EPO) Switch.

Technical Specification

MODEL EPIG+3010 EPIG+3015 EPIG+3020 EPIG+3030 EPIG+3060
Capacity 10KVA 15KVA 20KVA 30KVA 60KVA
INPUT
Nominal Voltage 380V/400V/415V/ SELECTABLE AC (3PH+N+PE, 5WIRE.), 220V / 230V / 240V AC
Operating Voltage Range 360V~470V AC Load Dependent
Operating Frequency Range 50 Hz + 1% (Auto Sensing)
Power Factor >0.9
OUTPUT
Output Voltage/Power Factor 220V / 230V / 240V AC / ±1% / 0.9 Optional
Output Frequency Auto Sensing 50Hz
Harmonic Distortion (THDv) <1% (Linear load), <3% (Non Liner Load)
Crest Factor 3:1
Efficiency Up to 94% Dual Conversion Mode, 99% ECO Mode
BATTERY
DC Voltage 120V/144V/180V 180/192V 220V 360V
Charge Current 10% of the Rated Battery AH
Recharge Time 8 Hours (90% of full capacity)
SYSTEM FEATURES
LCD Indication Input Voltage/Frequency, Output Voltage/Frequency
LED Indication Load Level, Battery Level, Line On, Battery On, Inverter On, By Pass, Fault & Reset Button
Alarms / Protection Batt. Low, DC High, Inverter Under/Over Voltage, UPS Over Load, Short Circuit, Fan Failure and UPS Fault.
Overload Capability <125% for 10 min, >125-150% for 1 min, >150% for 200 ms
Transfer Time AC to Battery : Oms, Inverter to Bypass : 4ms (Typical)
ENVIRONMENTAL
Temperature Operating: 0~40°C, Storage: -10°C ~ 55°C
Humidity / Altitude 0~95% RH Non-condersing / <1500 M
Noise Low Audible Noise Level
PHYSICAL
Dimension WxDxH (mm) 465x820x890 465x820x890 465x820x890
Weight (Kg) 90kg 125kgs 160kgs 175kgs
STANDARDS
Quality 1SO 9001, ISO 14001, OHSAS
Safety IEC/EN62040-1
EMC / Performance |EC/EN62040-2; IEC/EN62040-3, Complying to CE
COMMUNICATION INTERFACE
Standard RS-232 Optional
Optional SNMP / ModBus / Dry Contact / USB / RS-485
Technology Online Double conversion AC-DC-AC with high switching frequency VFI Inversion Technology IGBT Based Rectifier & Charger Section